The PAT300 series will carry out all test requirements automatically with one button press. PAT320 is the PAT tester if you need high productivity with a tough and easy to use instrument. If you are moving into PAT testing for the first time or you don’t want the complexity of database management, PAT320 is ideal for you.

PAT350 has additional flash test functions and is the ideal tester for high throughput requirements if you work in a tool hire company or a service centre. The PAT300 series provides outstanding productivity with the capability to test record numbers of appliances per hour. In addition to automatic testing, the ability to run each test individually is particularly well suited to service and repair organisations carrying out fault diagnostics.

Key Features:

  •   Simple manual or automatic testing
  •   230 V and 110 V operation
  •   Bond testing at 25 A,10 A and 200 mA
  •   Full colour display
  •   Tests portable RCDs and extension leads
  •   Outstanding productivity

FREE PAT testing accessories

Overview:

An easily portable desktop appliance tester for testing the safety of portable electrical equipment to meet health and safety regulations. The PAT300 series are fully featured testers with dedicated test buttons for direct access to tests. They are designed for customers who do not require the complexity of a fully configurable database of clients and results within the tester but do need a complete range of functions to allow automatic or manual testing of the widest range of electrical assets. There are two products in the range - the PAT320 and the PAT350. The PAT350 is identical to the PAT320, with the addition of flash-test capability for use in environments such as manufacturing, production or tool-hire shops. Simple push-button operation make the PAT300s fast and intuitive in use. All regulatory test requirements are supported, including Class I and Class II, IEC power leads, extension leads and full tests for portable RCDs. An automatic mode is available for Class I and Class II testing. In automatic mode, the tests proceed sequentially through bond, insulation and operation, indicating a pass or fail at each test. If a fail occurs, testing is stopped. When manual testing, each test is preceded by a selection screen where the test parameters are selected, such as bond test current, insulation test voltage or leakage test type. These diagnostic buttons provide direct access to any test individually, allowing single tests to be performed following repair or a suspect result. Accessories supplied with all models include a combined earth-bond and insulation test lead, an adaptor for testing extension leads, and a carry-case convenient product and lead storage.

 

Ideal Applications:

There is a legal requirement for any landlord, employer or owner of a place of work or public place, to ensure that all electrical equipment accessible by tenants, employees or the public is maintained in a safe condition, and an acceptable method of ensuring this is by routine electrical testing. This can be performed by electrical contractors, specialist PAT testing organisations, maintenance departments, or facilities management companies. The PAT300 range is suitable for performing portable appliance testing in locations such as hotels, public houses, schools, colleges, nurseries, shops, offices, theatres, banks, restaurants, cafés, sports and leisure facilities, cinemas, factories and hair salons etc. The PAT350 is suitable for use in tool-hire shops where equipment is routinely tested prior to hire.

Megger PAT320
Electrical Supply Range  
230V AC 230V AC ±10%
110V AC 110V AC ±10%
Supply Measurement  
Voltage ±2% ± 1V
Frequency ±1% ± 0.1Hz
Bond Test  
Open Circuit Voltage 9V AC ±10% ±0.1V (Supply: 230V 50Hz)
10A Bond Test Current 10A rms ±20% ±0.5A into 0.1Ω
25A Bond Test Current 25A rms ± 5% ± 0.5A into 0.1Ω
Earth Bond Resistance Accuracy ±5% ± 3 digits (0 to 0.49Ω)
±5% ± 5 digits (0.5 to .99Ω)
Earth Bond Resistance Resolution 10mΩ (0 to 1.99Ω)
Display Range 0 to 1.99Ω
Bond Test Nulling Up to 1.00Ω
Adjustable Test Duration User selectable from 1 sec to 20 sec
Continuity Test  
Note The continuity test is a DC test performed automatically
in both positive and negative directions. The average of
the two results is shown
Continuity Test Voltage 4.0V DC -0% +10% (open circuit)
Continuity Test Current 200mA -0% + 10% ± 5mA (into 2Ω load)
Continuity Resistance Accuracy ±5% ±3 digits (0 to 0.49Ω)
±5% ±5 digits (0.5 to .99Ω)
Continuity Resistance Resolution 10mΩ (1 to 19.99Ω)
Display Range 0 to 19.99Ω
Continuity Test Nulling Up to 9.99Ω
Test Duration User selectable from 1 sec to 20 sec
Insulation Test  
Insulation Test Voltage 250V DC -0%/+25% open circuit
500V DC -0%/+25% open circuit
(500V DC across 0.5MΩ)
Insulation Resistance Accuracy (230V) ±2% ±5 digits (0 to 19.99MΩ)
±5% ± 10 digits (20 to 99.99MΩ)
Insulation Resistance Accuracy (110V) ±5 ±5 digits (0 to 10MΩ)
Insulation Resistance Resolution 0.01MΩ (0.10 to 99.99MΩ)
Display Range 0 to 99.99MΩ
Test Duration User selectable from 1 sec to 1 minutes
Substitute Leakage Test  
Test Voltage 40V AC ±10%
Test Frequency Nominal mains 50/60Hz
Leakage Current Accuracy ±5% ± 5 digits
Leakage Current Resolution 0.01mA
Display Range 0 to 19.99mA
Test Duration User selectable from 1 sec to 1 minute
Reading corrected to 230V + 10% or 110V +10% AC
Differential Leakage Current  
Test Voltage Nominal mains 110V/230V AC
Test Frequency Nominal mains 50/60Hz
Differential Leakage Current Accuracy ±5% ± 5 digits
Differential Leakage Current Resolution 0.01mA
Display Range 0 to 19.99mA
Reading corrected to 230V +10 % or 110V + 10% AC
Touch Current Test  
Test Voltage Nominal mains 1150/230V AC
Test Frequency Nominal mains 50/60Hz
Touch Current Accuracy ±5% ±5 digits
Touch Current Resolution 0.01mA
Display Range 0 to 10mA
Test Duration User selectable from 1 sec to 5 sec
Reading corrected to 230V + 10% or 110V + 10% AC
Operational Test  
Test Voltage Nominal mains 110V/230V AC
Accuracy ±5% ±10 digits (0 to 99VA)
±5% ±50 digits (100 to 999VA)
±5% ±100 digits (1000 to 3700VA)
Resolution 1VA (0 to 3700VA)
Display Range 0 to 3.99KVA
Reading corrected to 230V or 110V AC
Results show load VA
Extension Lead Test  
Polartity Test Voltage 12V
Polarity Leak OK
Live neutral S/C
Live neutral reversed
Live/neutral O/C
Portable RCD Test  
RCD Test Voltage Nominal mains 110/230V
RCD Test Frequency 50Hz
Test Current Accuracy -8% to -2% (1/2 x I)
±2% to +8^ (1 x 1,5 x I)
Trip Time Accuracy ±1% ±5 digits
Trip Time Resolution 0.1ms
Display Range 0 to 1999ms (1/2 x I)
0 to 300ms (1 x I)
0 to 40ms (5 x I)
Fuse Test  
Test Voltage 3.3V
Warning Audible Beep if fuse is ok