Martindale HPAT500-2 Portable Appliance Tester

Product Code: MARHPAT500-2

Price
£339.95 ex. VAT £407.94 inc. VAT

Available In 3-7 Days


Add To Favourites
Detailed Description

The HPAT500 is an easy to use battery powered, hand held PAT tester with simple one-button test selection. It’s lightweight portable design make it ideal for testing in all locations whether under a desk or testing a wall mounted monitor. The tester comes with rechargeable batteries and mains charger for low cost of ownership and can even be used whilst recharging ensuring no downtime.

A single button press activates either a full Class I, Class II or lead test without any further interaction required by the user, unless a failure is encountered. The display has clear PASS / FAIL indicators and shows all test results on screen. Simple connection diagrams are permanently shown on the case body making it easy to start testing straight away. This is an ideal tester for the occasional or low volume tester. A comprehensive range of optional adaptor leads are available enabling 110V appliance testing and testing of equipment terminated with 3 phase plugs.

Key Features:

  • Compact design with backlit display
  • Easy one button testing
  • Automatic Class I, Class II & power lead tests
  • Measured values with clear PASS/FAIL indication
  • 200mA earth bond test - I.T. Safe
  • 250V / 500V insulation test
  • Mains rechargeable
  • New high contrast backlit display
  • Now includes 250v and 500v insulation tests

FREE PAT testing accessories



HPAT500-2 Comes Supplied With:

  • Mains charger
  • TL67 earth bond probe
  • 6 x AA NiMH rechargeable batteries
  • EX322 IEC adaptor lead
  • TC68 carry case

HPAT selection

Martindale HPA500 Portable Appliance Tester
Earth Continuity  
Test Voltage 4V DC (into open circuit)
Test Current 200mA DC (into short circuit)
Range 0 to 19.99Ω
Resolution 0.01Ω
Accuracy ± (5% of reading + 2 digits)
Fixed Pass Limits  
Lead ≤ 0.10 Ω = PASS
≤ 0.20 Ω = NOTE x.xx PASS
Class I Class I ≤ 0.10 Ω = PASS
≤ 0.20 Ω = NOTE x.xx PASS
Insulation  
Fixed Voltage >500V DC at 1mA (< 600V DC into open circuit)
Test Current Test current: 1.5mA (into short circuit)
Ranges 2.00MΩ, 20.0MΩ, 200MΩ
Resolution 0.01MΩ
Accuracy <100MΩ ± (5% reading + 2 digits)
>100MΩ ± (10% reading + 2 digits)
Fixed Pass Levels Lead: ≥ 1.0 MΩ
Class I: ≥ 1.0 MΩ
Class II: ≥ 2.0 MΩ
Fuse Checks  
Test Voltage 4V DC (into open circuit)
Test Current 200mA DC (into short circuit)
Pass Level >2mA
General  
Overload Protection 300V AC/DC
Protection Class IP20
Safety Complies to BS EN 61010-1: 2001
Temperature Range -10 to 40°C, non-condensing
Batteries 6 x 1.2V AA NiMH rechargeable batteries
1800mAh, or greater
Battery Life Fully charged, minimum 600 complete
tests. The HPAT500 will operate fully from the battery
charger in the event of discharged batteries. Do not
remove batteries.
Auto Shut Down After 10 minutes of inactivity, or when battery low
Battery Charger Input 230V 50Hz
Battery Charger Output 12VDC at 300mA, 5.5 jack x 2.5 bore centre
positive
Dimensions 90 x 210 x 54mm
Weight Approx 700g (including batteries & leads)
UK Mainland Order by 2pm for Next Day Delivery*
Under £25.00 £4.50
Over £25.00 FREE

UK Highlands & Islands Order by 2pm for Next Day Delivery*
Under £80.00 £15.00
Over £80.00 FREE