Product Code: DILALVAMFT
In Stock
Designed for accuracy and ease of use, the ALVA MFT features a vivid full-colour TFT display with interactive controls, allowing users to set pass/fail conditions effortlessly. It supports a full range of RCD types, including AC, A, B, B+, EV and F, making it a versatile solution for modern electrical installations.
The ALVA MFT Installation Multifunction Tester simplifies testing with automated Continuity & Earth Loop Auto Start, accompanied by a secondary display for recorded results. Its intelligent 2/3 wire high-current loop detection eliminates the need for manual selection, automatically identifying whether a 2-wire or 3-wire Loop/PSCC measurement is being conducted.
For enhanced customisation, the variable RDC test feature enables users to dial in bespoke mA values, ensuring greater flexibility across different testing scenarios. The ALVA MFT also includes 6mA RDC-PD/MD testing, allowing electricians to safely and accurately verify the performance of EVSE chargers as part of electric vehicle infrastructure installations.
Additionally, the ALVA MFT is equipped with inbuilt fuse tables, which indicate the maximum permitted Zs Loop values when carrying out Earth Loop Impedance testing—helping electricians maintain compliance with industry safety standards.
Whether working on domestic, commercial, or industrial installations, this state-of-the-art tester delivers outstanding value and uncompromising accuracy. Designed for compliance, efficiency, and reliability, the ALVA MFT is the ultimate solution for professionals seeking affordable next-generation electrical testing.
Upgrade your testing experience with the Di-LOG ALVA MFT—precision, reliability, and compliance in one powerful device.
ALVA MFT Technical Specifications |
||
|---|---|---|
Measurement Range |
Resolution |
Basic Accuracy |
Voltage & Frequency |
||
| AC Voltage TRMS 0V - 550V |
1V | ±2% ± 2 dgts |
| DC Voltage 0V - 550V |
1V | ±2% ± 2 dgts |
| Frequency 10 - 499Hz |
0.1Hz | ±0.2% ± 1 dgts |
Phase Rotation |
||
0V - 550VMeasurement range BS EN 61557-7 |
Right:1-2-3 ; Left: 3-2-1 | |
Continuity |
||
| Low R (200mA) | 0.01Ω - 19.99Ω 20.1Ω - 99.9Ω 100Ω - 1999Ω |
±3% ± 3 dgts ±5% ± 5 dgts ±5% ± 5 dgts |
Insulation |
||
50V, 100V & 250V(50kΩ-80MΩ @ 50V | 100kΩ-199.9MΩ @ 100V & 250V) |
<0.01MΩ - 19.999MΩ 19.99MΩ - 99.99MΩ 20.0MΩ - >199.9MΩ |
±5% ± 3 dgts ±5% ± 3 dgts ±5% ± 5 dgts |
500V & 1000V(500kΩ-199.9MΩ @ 500 & 1000V) |
<0.01MΩ - 19.999MΩ 19.99MΩ - 99.99MΩ 20.0MΩ - >199.9MΩ 200MΩ - >999MΩ |
±5% ± 3 dgts ±5% ± 3 dgts ±5% ± 5 dgts ±10% |
Line Impedance (L-L | L-N) |
||
0.20Ω - 9999ΩMeasurement range BS EN 61557-3 is 0.25Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts |
Perspective Short Circuit Current (PSC) |
||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
Earth Fault Loop Impedance (Z-loop L-PE High Current) |
||
0.20Ω - 9999ΩMeasurement range BS EN 61557-3 is 0.25Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 5 dgts |
Perspective Earth Fault Current (PFC - High Current) |
||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
Earth Fault Loop Impedance (Z-Loop (Zs) Non-Trip) |
||
| 0.40Ω - 19.99Ω 20.0Ω - 9999Ω Measurement range BS EN 61557 is 0.75Ω - 1999Ω |
0.01Ω - 19.99Ω 20.0Ω - 99.9Ω 100Ω - 9999Ω |
±5% ± 10 dgts ±10% |
Perspective Earth Fault Current (PFC-Non-Trip) |
||
| 0.00A - 19.99A 20.0A - 99.9A 100A - 999A 1.00kA - 9.99kA 10.0kA - 100.0kA |
0.01A 0.1A 1A 0.01kA 0.1kA |
Calculated value taking into account the Earth Loop Accuracy of ±5% ± 5 dgts |
RCD Tripping Time |
||
0.0 - 500.0ms(Measurement range BS EN 61557-6) |
0.1ms | ±3ms |
| Test Current - ½ x I∆n | 1 x I∆n | 2x I∆n | 5 x I∆n | ||
| RCD Types- AC | A | B | B+ | EV | F | S (Selective - Time Delayed) | ||
RCD Tripping Current |
||
0.0 - 500.0ms(Measurement range BS EN 61557-6) |
0.1ms | ±3ms |
| 0.2 x IΔn - 1.1 IΔn (AC type) 0.2 x IΔn - 1.5 IΔn (A type, IΔn ≧30mA ) 0.2 x IΔn - 2.2 IΔn (A type, IΔn ≧10mA ) 0.2 x IΔn - 2.2 IΔn (B type) |
0.05 x IΔn | ±0.1 x IΔn |
| Nominal RCD Currents- 6mA | 10mA | 30mA | 100mA | 300mA | 500mA | ||
Contact Voltage |
||
| 3.0V - 9.9V 10.0V - 99.9V |
0.1V | -0/+10% ±10 dgts |
General Information |
||
| EN61010 Overvoltage Safety Rating | CAT III 600V | CAT IV 300V |
| Display | 480 x 320 TFT | LCD Screen |
| Power supply | 6 x AA Alkaline batteries (included) | |
| Recharge Option | ALVA Recharge Pack A available | |
| Dimensions | 250 x 107 x 135 mm | |
| Weight | 1300g (Excluding batteries) | |
| UK Mainland | Order by 2pm for Next Day Delivery* |
|---|---|
| Under £25.00 | £4.50 |
| Over £25.00 | FREE |
| UK Highlands & Islands | Order by 2pm for Next Day Delivery* |
|---|---|
| Under £80.00 | £15.00 |
| Over £80.00 | FREE |