Specifications: Fluke 1770 Series Three-Phase Power Quality Analyzers
Key features
Voltage inputs |
Number of inputs |
4 inputs, 3 phases and neutral referenced to PE (5 connectors) |
Measurement category |
1000 V CAT III / 600 V CAT IV |
Maximum input voltage |
1000 V rms / 1000 V dc (1700 Vpk) |
Nominal voltage range |
Wye and single phase: variable (50 V – 1000 V) Delta: Variable (100 V – 1000 V) IEC 61000-4-30 Class A compliance for the nominal voltages (Vdin) 100 V – 690 V |
Input impedance |
10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE |
Bandwidth |
DC to 30 kHz for PQ measurements, excluding transients |
Resolution |
24-bit synchronous sampling |
Sampling frequency |
80 kS/s at 50/60 Hz |
Scaling |
1:1, variable for use of potential transformers |
Voltage transients |
Measurement range |
±8 kV |
Sampling rate |
1775: 1 MS/s 1777: 1 MS/s, 20 MS/s |
Bandwidth |
DC to 1 MHz |
Trigger |
Adjustable trigger level. Triggers on high-frequency components > 1.5 kHz |
Resolution |
14-bit synchronous sampling |
Current inputs |
Number of inputs |
4 inputs 3 phases and Neutral, range selected automatically to attached sensor |
Range |
AC |
1 A to 1500 A with i17XX-FLEX1500 12 1 A to 1500 A with i17XX-FLEX1500 24 3 A to 3000 A with i17XX-FLEX3000 24 6 A to 6000 A with i17XX-FLEX6000 36 40 mA to 40 A with clamp i40s-EL 4 A to 400 A with clamp i400s-EL |
DC |
20 A to 2000 A with 80i-2010-EL clamp |
Bandwidth |
DC to 30 kHz |
Resolution |
24-bit synchronous sampling |
Sampling frequency |
80 kS/s at 50/60 Hz |
Scaling |
1:1, variable |
Input voltage |
Clamp: 50 mV / 500 mV rms; CF 2.8 Rogowski Coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz; CF 4 all at nominal probe range |
Input impedance |
11 kΩ |
Aux inputs |
Wired connection with 17XX-AUX adapter |
Number of inputs |
2 |
Input range |
Direct: 0 V dc to ± 10 V dc 0 V to 1000 V dc |
Input impedance |
Direct: 2.92 MΩ |
Scale factor |
Format: mx + b (gain and offset) user configurable |
Displayed units |
User configurable (up to 8 characters, for example °C, psi, or m/s) |
Data acquisition voltage and current |
Input mains frequency |
DC, 50/60 Hz 15 % (42.5 Hz … 57.5 Hz, 51 Hz … 69 Hz) |
Topologies |
1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye IT, 3-φ Aron/Blondel (2 element delta), 3-φ delta open leg, 3-φ high leg delta |
Data storage |
Fluke 1773/1775: 8 GB internal (expandable with microSD card) Fluke 1777: 32 GB microSD card (installed) |
Memory size |
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 100 events. The number of possible logging sessions and logging period depends on user requirements |
Real time accuracy |
Internal: 3 ppm (0.26 s per day, 8 s per month) NTP (internet time): Depending on internet latency, typical < 0.1 s absolute to UTC GPS: < 1 ms absolute to UTC |
Trend interval |
Measured parameter |
See operator manual |
Trend interval |
User selectable: 1 sec, 3 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
Averaging interval min/max values |
Voltage, Current: ½ cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 Hz) Aux, Power: 200 ms |
Total harmonic distortion |
THD for voltage and current is calculated on 50 harmonics |
Power quality measurements |
Measured parameter |
See operator manual |
Harmonics |
h0 … h50 % fund and RMS for voltage, current and power Phase angles for voltage and current up to h11 |
Interharmonics |
ih0… ih50 % fund and RMS for voltage and current |
Supraharmonics |
2–9 kHz with 200 Hz bins 9–30 khz with 2 kHz bins RMS for voltage and current |
Harmonics measurement method |
Grouped, sub-grouped and single harmonic bins according to IEC 61000-4-7. Method selected automatically based on configured PQ standard or user configurable. |
Total harmonic distortion |
Calculated on up to 50 harmonics (depends on selected PQ standard) |
Mains signaling |
2 frequencies in the range from 110 Hz to 3000 Hz |
Events |
Voltage |
Dip, swell, interruption, rapid voltage change, mains signaling, waveshape deviation, transients |
Current |
Inrush current |
Triggered recordings |
Half cycle RMS of voltage and current for 10 s Waveform of voltage and current for 10/12 cycles Mains signaling: 200 ms RMS of mains signaling voltage up to 120 s Transients: Waveform of voltage (Fluke 1777: 1 MS/s or 20 MS/s, 500,000 pts, Fluke 1775: 1 MS/s, 25,000 pts) |
Standard compliance |
Power |
IEEE 1459 |
Harmonics |
IEC 61000-4-7: Class 1 IEEE 519 (short time and very short time harmonics) |
Flicker |
IEC 61000-4-15 Class F1 |
Power quality |
IEC 61000-4-30 Class A, IEC 62586 PQI-A-PI |
Power quality compliance |
EN 50160 + GOST + NEQUAL + NETCODE + FOL |
Interfaces |
Ethernet |
1 Gbit/s 1000BASE-T |
USB type A |
USB 2.0 high speed for USB flash drives to transfer measurement data, firmware updates and license installation. Max. supply current: 500 mA |
USB-C |
USB 2.0 high speed for data download to PC and calibration (requires USB type A to USB-C or USB-C to USB-C cable) Auxiliary power supply for the Analyzer (requires USB C power adapter PD 2.0 or higher with 9 V 1.8 A support) USB 3.0 super-speed for USB-C flash drives to transfer measurement data, firmware updates and license installation. Max. supply current: 900 mA |
WiFi/BLE module1 |
802.11 ac 2.4 GHz / 5 GHz, support for concurrent access point and client mode Bluetooth 5.0/BLE Antenna: Internal and external2 |
LTE/4G module3 |
LTE-A Cat 12 Worldwide LTE-A and UMTS/HSPA+ coverage Antenna: External2 |
GPS |
MCX connector to attach a GNSS antenna for GPS/GLONASS2 |
1 Not in 177X/BASIC versions 2 Requires 5m extension cable, Fluke p/n 5263915 3 Availability and supported providers vary by country. Check with your local Fluke representative. |
Electrical measurement accuracy
Parameter |
Range |
Resolution |
Intrinsic Accuracy at Reference Conditions % of Reading + % of Full Scale |
Voltage |
1000 V |
0.1 V |
0.1 % of nominal voltage in accordance with IEC 61000-4-30 Class A1,2 ±(0.04 % + 0.004 %)3 |
Voltage dips and swells |
- |
0.1 V |
0.2 % of Vnom1,2 |
Voltage transients |
±8 kVpk |
- |
±5 % +0.25 %) |
Voltage harmonics/interharmonics |
100 % |
0.1 % / 0.1 mV |
≥1 % Vnom1: ±2.5 % of rdg. <1 % Vnom1: ±0.025 Vnom |
THD on voltage |
100 % |
0.1 % / 0.1 V |
±(2.5 % + 0.5 %) |
Voltage distortions 2-9 kHz |
Max 100 V |
0.1 mV |
±(2.5 % + 0.1 V) |
Voltage distortions 9-30 kHz |
Max 100 V |
0.1 mV |
±(2.5 % + 0.1 V) |
Current (Rogowski clamp mode) |
With iFlex 1500 A, i17XX-FLEX1500 24 |
150 A 1500 A |
0.01 % 0.1 A |
±(1 % + 0.02 %) |
With iFlex 3000 A, i17XX-FLEX3000 24 |
300 A 3000 A |
0.01 A 0.1 A |
±(1 % + 0.03 %) |
With iFlex 6000 A, i17XX-FLEX6000 36 |
600 A 6000 A |
0.1 A 1 A |
±(1.5 % + 0.03 %) |
With AC clamp 40 A, i40s-EL |
4 A 40 A |
0.001 A 0.01 A |
±(0.7 % + 0.02 %) |
With AC clamp 400 A, i400s-EL |
40 A 400 A |
0.01 A 0.1 A |
±(2 % + 0.2 %) ±(0.7 % + 0.1 %) |
With AC/DC clamp 2000 A, 80i-2010s-EL |
200 A 2000 A |
0.01 A 0.1 A |
±(0.8 % + 0.2 %) |
Current min/max |
100 % |
defined by accessory |
x2 of intrinsic accuracy |
Current harmonics/interharmonics |
100 % |
0.1 % / 0.01 A |
≥3 % Inom: ±2.5 % of rdg.4 <3 % Inom: ±0.15 % of Inom |
THD on current |
100 % |
0.1 % |
±(2.5 % + 0.5 %) |
Frequency |
42.5 Hz … 69 Hz |
0.001 Hz |
±0.01 Hz |
Voltage unbalance |
100 % |
0.1 % |
±0.15 % |
Current unbalance |
100 % |
0.1 % |
±0.15 % |
Flicker Pinst, Pst, Plt |
0 to 20 |
0.01 |
5 % |
Mains signaling voltage |
Up to 3 kHz 0-15 % of Vnom |
0.1 V / 0.1 % |
1-3 % Vnom: ±0.15 % of Vnom 3-15 % Vnom: ±5 % of rdg. |
AUX input |
±10 V |
0.1 mV |
±(0.2 % + 0.05 %) |
1 Nominal voltage in the range of 100 V to 690 V. Also known as Udin. 2 0 °C to 45 °C: Intrinsic Accuracy x2. Outside of 0 °C to 45 °C: Intrinsic Accuracy x3 3 Only for calibration laboratories 4 With iFlex 1500A, I17XX-FLEX1500 24 |
Power/Energy
Parameter |
Direct Input1 |
Clamp i40S-EL |
Power range W, VA, var |
Clamp: 50 mV / 500 mV Rogowski: 15 mV / 150 mV |
4 A / 40 A |
Clamp: 50 W / 500 W Rogowski: 15 W / 150 W |
4k W / 40 kW |
Max. resolution W, VA, var |
0.1 W |
1 W / 10 W |
Phase (voltage to current)1 |
±0.2° |
±1° |
Parameter |
iFlex 1500A, I17XX-FLEX1500 24 |
iFlex 3000A, I17XX-FLEX3000 |
iFlex 6000A, I17XX-FLEX6000 |
Power range W, VA, var |
150 A / 1500 A |
300 A / 3000 A |
600 A / 6000 A |
150 kW / 1.5 MW |
300 kW / 3 MW |
600 kW / 6 MW |
Max. resolution W, VA, var |
0.1 kW / 1kW |
1 kW /10 kW |
1 kW / 10k W |
Parameter |
|
I17XX-FLEX1500 24 |
I17XX-FLEX3000 |
I17XX-FLEX6000 |
Active power P |
PF ≥ 0.99 |
150 A / 1500 A |
300 A / 3000 A |
600/6000 A |
1.2 % + 0.005 % |
1.2 % + 0.0075 % |
1.7 % + 0.0075 % |
Active energy Ea |
0.1 ≤ PF < 0.99 |
(1.2+√(1-PF2)/(2 PF)) % + 0.005 % |
(1.2+√(1-PF2)/(2 PF)) % + 0.0075 % |
(1.7+√(1-PF2)/(2 PF)) % + 0.0075 % |
Apparent power S Apparent energy Eap |
0 ≤ PF ≤ 1 |
1.2 % + 0.005 % |
1.2 % + 0.0075 % |
1.7 % + 0.0075 % |
Reactive power Q Reactive energy Er |
0 ≤ PF ≤ 1 |
2.5 % of measured apparent power/energy |
Additional uncertainty (% of power high range) |
VP-N > 250 V |
0.02 % |
0.02 % |
0.02 % |
Phase (voltage to current) |
- |
0.28° |
0.28° |
0.28° |
1 Nominal voltage in the range of 100 V to 690 V. Also known as Udin.
Reference Conditions
Environmental: 23 °C ±5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 %
Input conditions: Cos Φ/PF=1, Sinusoidal signal f=50/60 Hz, power supply 120 V/230 V ±10 %.
Current and power specifications: Input voltage >100V
Input current > 10 % of current range
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient: Add 0.1 x specified accuracy for each degree °C above 28 °C or below 18 °C
|
General specifications
Key features |
Warranty |
Analyzer: 2 years (battery not included) Accessories: 1 year (including battery) |
Calibration cycle |
2 years |
Size (L X W X HD) |
28.0 cm x 19.0 cm x 6.2 cm (11.0 in x 7.5 in x 2.4 in) |
Weight |
2.1 kg (4.6 lb) |
Anti-theft protection |
Slot to support Kensington lock |
Environmental specifications |
Operating temperature range |
-10 °C to 50 °C |
Storage temperature range |
-20 °C to 60 °C |
Operating humidity |
IEC 60721-3-3: 3K5, modified: -10 °C to 30 °C: ≤95 %, no condensation or ice 35 °C: 70 % 40 °C: 55 % 50 °C: 35 % |
IP Rating |
IEC 60529: IP50 |
Vibration |
IEC 60721-3-3 / 3M2 |
Power supply |
Voltage range |
100 V – 600 V -15 % / +10 % (85 V … 660 V) |
Power consumption |
Max. 40 VA1 |
Mains frequency |
50/60 Hz (42.5 Hz … 69 Hz) |
UPS |
Li-Ion battery BP1770 with extended temperature range, customer replaceable On-battery runtime: 1.5 hours |
Safety |
General |
IEC 61010-1: Pollution Degree 2 |
Power supply |
Overvoltage Category IV 600 V With Mains Adapter MA-C8: Overvoltage Category II 300 V |
Measurement |
IEC 61010-2-030: CAT IV 600 V, CAT III 1000 V |
Altitudes 2000 m to 4000 m |
Derate to: Power Supply: Category IV 300 V With MA-C8 Adapter: Category II 150 V Measurement: CAT IV 300 V, CAT III 600 V, CAT II 1000 V |
|