Key Features:

  • Programmable Auto sequences.
  • Predefined profile dependent Auto sequences
  • Predefined Automatic tests: 
  • - Auto TT (U, Zln, Zs, Uc); 
  • - Auto TN/RCD (U, Zln, Zs, Rpe); 
  • - Auto TN (U, Zln, Zlpe, Rpe); 
  • - Auto IT (U, Zln, Isc, Isfl, IMD).
  • Functional inspections.
  • Visual inspections.
  • Custom inspections (visual and functional) which may be incorporated into Auto sequences
  • EVSE AUTO SEQUENCEs and function inspections.
  • Machine functional and visual inspections.
  • Built-in help screens for referencing on site.
  • Built-in fuse tables for automatic evaluation of the line / loop impedance result.
  • Monitoring of all 3 voltages in real-time.
  • Automatic polarity reversal on continuity test.
  • Automated RCD testing procedure (RCD AUTO).
  • Automated Impedance testing procedure (Z AUTO).
  • Measurement filtering according to the selected area group.
  • Built-in charger and rechargeable batteries as standard accessory.
  • BT communication with PC, Android tablets and smart phones via built-in BT.

Calibration information
This instrument comes complete with a manufacturers calibration certificate. Please be aware that these certificates are generic and may also be time lapsed. If you would prefer a personalised full traceable calibration certificate applied to the equipment before dispatch, then please select this option from the drop-down menu above, an additional calibration charge will apply.

FREE Gifts

This instrument comes complete with your choice of free gift from the drop-down menu above. Choose from a calibration voucher for next 
year, a 50m R2 wander lead or a set of quality silicone test leads. How about a quality socket tester or a lock off kit? 
Whatever you choose you can be sure you're getting a fantastic deal at Instrument Sales & Services.

Standard Set

(For the MI 3155 EurotestXD Euro Set please follow this link)

MI 3155 EurotestXD is the newest flagship of Metrel’s most advanced line of multi-functional measuring instruments and is designed specifically for testing in industry. What differentiates this instrument from the rest is its ergonomic design and an intuitive user interface, encompassing a memory organizer and fully programmable AUTO SEQUENCEs, managed through a large colour touch screen display.

It is fully compliant with functionality standards (e.g. IEC/EN 61557) and other reference standards for testing (e.g. IEC/EN/ HD 60364-4-41,...) as is required for any instrument that performs TRMS current measurements, RCD tests, line and loop impedance tests with 3 (and 4) wires and earth resistance measurements.

Besides those, the instrument supports a wide range of tests and measuring functions, including on-line voltage monitoring, phase sequence testing, varistor testing, PI/DAR calculation, luminance measurement, discharge time testing, ISFL measurements, IMD tests as well as functional and visual inspections.

MI 3155 Standard Set Comes Supplied With:

  • Instrument MI 3155 EurotestXD
  • 4400 mAh battery pack
  • Power supply adapter 12V/3A
  • Tip commander + 2 x bat. AAA
  • Mains plug cable 1,5 m
  • Test lead green 1,5 m
  • Test lead, 4-wire, 1,5 m
  • Test lead, 3-wire, 1,5 m
  • Test lead, 2-wire, 2,5 kV, 1.5 m
  • Test probe, 6 pcs (black, brown, blue, green-2, red)
  • Crocodile clip, 7 pcs (black-2, brown, blue, green, red-2)
  • Earth set, 3-wire 20 m
  • USB cable
  • Soft carrying bag
  • Soft carrying neck belt
  • Metrel ES Manager BASIC license*
  • Short instruction manual
  • Instruction manual (CD)
  • Guide for testing and verification of Low voltage installations (CD)
  • Calibration certificate
  • Metrel ES Manager (program installation) A 1481 (CD)

MEASURING FUNCTIONS:

  • Live Transformer’s Impedance Measurement with Four Wire Test;
  • Hi-precision Short Circuit Current evaluation with Calculated Hot factor;
  • 3-wire test of PE (RPE function) without extension lead conductor;
  • Autotest insulation function between L-N, N-PE and L-PE (R ISO ALL function);
  • 4 wire continuity test;
  • Insulation resistance with DC voltage from 50 V to 2500 V and PI, DAR calculation;
  • Varistor test;
  • Continuity of PE conductors with 200 mA DC test current with polarity change;
  • Continuity of PE conductors with 7 mA test current without RCD tripping;
  • 2-wire and 3-wire loop impedance (L-PE) measurement with Trip Lock RCD function;
  • Touch voltage / Contact voltage measurement with external P/S probe.
  • 2-wire and 3-wire line impedance (L-L, L-N) measurement;
  • 1-phase / 3-phase TRMS voltage and frequency measurements;
  • Line, loop and RCD measurements at frequency range 16 ... 400 Hz;
  • Phase sequence; • Power and THD measurement (up to the 12th harmonic);
  • RCD testing (general and selective, type AC, A, F, B, B+, MI RCD, EV RCD, PRCD, PRCD-K, PRCD-S);
  • Earth resistance (3-wire and 2-clamps method);
  • Specific earth resistance with Ro-adapter (option);
  • TRMS leakage and load currents (option);
  • First fault leakage current (ISFL);
  • Testing of Insulation Monitoring Devices (IMDs);
  • Machine mode support with time discharge;
  • Illumination (option);
  • High resolution Loop impendance (mΩ) (option);
  • EVSE (Electrical Vehicle Supply Equipment) support (option);
  • Determining location of cables (option);
  • QR and/or barcode scanner support (option).

Applications:

Electrical Power Systems

  • Power Plants
  • Distribution
  • Safety
  • Connections / Bondings
  • Insulation Analysing
  • Earthings / Funnels

Industrial Systems

  • LV Installations Safety / Quality
  • UPS Systems testing
  • Switchboards / Controlgears
  • Machines / Power Loads
  • Working Places Health / Safety Care
  • Maintenance / Troubleshooting
  • 3-phase system testing

Buildings Facility Management

  • Public areas Safety / Quality
  • Fire Safety
  • Risk Assessments
  • Environmental Issues

Metrel MI 3155 EurotestXD
Function Specification Measuring Range Resolution Accuracy 
                      CONTINUITY Test Current 7 mA 2-wire

0.00 Ω ... 19.99 Ω

20.0 Ω ... 1999 Ω

0.1 Ω

1 Ω

±(5 % of r. + 3 digits)
Test Current 200 mA 2-wire, 4-wire

0.00 Ω ... 19.99 Ω

20.0 Ω ... 199.9 Ω

200.0 Ω ... 1999 Ω

0.01 Ω

0.1 Ω

1 Ω

±(3 % of r. + 3 digits)

±(5 % of r.)

±(5 % of r.)

          INSULATION RESISTANCE

R iso, R iso all 1

Test Voltage 50/100/250 V

0.00 MΩ ... 19.99 MΩ

20.0 MΩ ... 99.9 MΩ

100.0 MΩ ... 199.9 MΩ

0.01 MΩ

0.1 MΩ

0.1 MΩ

±(5 % of r. + 3 digits)

±(10 % of r.)

±(20 % of r.)

R iso, R iso all 1

Test Voltage 500/1000 V

0.00 MΩ ... 19.99 MΩ

20.0 MΩ ... 199.9 MΩ

200 MΩ ... 999 MΩ

0.01 MΩ

0.1 MΩ

1 MΩ

±(5 % of r. + 3 digits)

±(5 % of r.)

±(10 % of r.)

R iso, R iso all 1

Test Voltage 2500 V

0.00 MΩ ... 19.99 MΩ

20.0 MΩ ... 199.9 MΩ

200 MΩ ... 999 MΩ

1.00 GΩ ... 19.99 GΩ

0.01 MΩ

0.1 MΩ

1 MΩ

0.01 GΩ

±(5 % of r. + 3 digits)

±(5 % of r.)

±(10 % of r.)

±(10 % of r.)

DAR, PI

0.01 ... 9.99

10.0 ... 100.0

0.01

0.1

±(5 % of r. + 2 digits)

±(5 % of r.)

Varistor test AC, DC 2

0 V … 1000 V (DC)

0 V … 625 V (AC)

1V ±(3 % of r. + 3 digits)
                            RCD RCD Uc

0.00 V ... 19.99 V

20.0 V ... 99.9 V

0.1 V

-0 %/+15 %) of r. ± 10 digits

(-0 %/+15 %) of r

RCD (t),

0.00 ms ... 40.0 ms

0.0 ms ... max. time

0.1 ms

±1 ms

±3 ms

RCD I Ramp

0.2xI∆N ... 1.1xI∆N (AC, MI, EV a.c.)

0.2xI∆N ... 1.5xI∆N (A, I∆N ≥30 mA)

0.2xI∆N ... 2.2xIvN (A, I∆N <30 mA)

0.2xI∆N ... 2.2xI∆N (B, MI, EV d.c.)

0.05xI∆N ±0.1xI∆N
                      IMPEDANCE

Zline (L-L, L-N), Ipsc,

Zline 4-wire 3

0.00 Ω ... 9.99 Ω

10.0 Ω ... 99.9 Ω

100 Ω ... 999 Ω

1.00 kΩ ... 9.99 kΩ

0.01 Ω

0.1 Ω

1 Ω

10 Ω

±(5 % of r. + 5 digits)

±(10 % of r.)

                       IMPEDANCE

Zloop (L-PE), Ipfc,

Zloop 4-wire 3

0.00 Ω ... 9.99 Ω

10.0 Ω ... 99.9 Ω

100 Ω ... 999 Ω

1.00 kΩ ... 9.99 kΩ

0.01 Ω

0.1 Ω

1 Ω

10 Ω

±(5 % of r. + 5 digits)

±(10 % of r.)

                        VOLTAGE TRMS (0, 14 ... 500 Hz) 0 … 550 V 1 V ±(2 % of r. + 2 digits)
Frequency

0.00 Hz .. 9.99 Hz

10.0 Hz ... 499.9 Hz

0.01 Hz

0.1 Hz

±(0.2 % of r. + 1 digits)
                       CURRENT TRMS, AC with A 1018, range=20 A

0.0 mA ... 99.9 mA

100 mA ... 999 mA

1.00 A ... 19.99 A

0.1 mA

1 mA

0.01 A

±(5 % of r. + 5 digits)

±(3 % of r. + 3 digits)

±(3 % of r.)

TRMS, AC with A 1019, range=20 A

0.0 mA ... 99.9 mA

100 mA ... 999 mA

1.00 A ... 19.99 A

0.1 mA

1 mA

0.01 A

Indicative

±(5 % of r.)

±(3 % of r.)

TRMS, AC/DC with A 1391, range=40 A

0.00 A ... 1.99 A

2.00 A ... 19.99 A

20.0 A ... 39.9 A

0.01 A

0.01 A

0.1 A

±(3 % of r. + 3 digits)

±(3 % of r.)

±(3 % of r.)

TRMS, AC/DC with A 1391, range = 300 A

0.00 A ... 19.99 A

20.0 A ... 39.9 A

40.0 A ... 299.9 A

0.01 A

0.1 A

0.1 A

Indicative

Indicative

±(3 % of r. + 5 digits)

             EARTH RESISTANCE 3 wire

0.00 Ω ... 19.99 Ω

20.0 Ω ... 199.9 Ω

200.0 Ω ... 9999 Ω

0.01 Ω

0.1 Ω

1 Ω

±(5 % of r. + 5 digits)
2 clamp

0.00 Ω ... 19.99 Ω

20.0 Ω ... 30.0 Ω

30.1 Ω ... 39.9 Ω

0.01 Ω

0.1 Ω

0.1 Ω

±(10 % of r. + 10 digits)

±(20 % of r.)

±(30 % of r.)

Specific earth resistance

0.0 Ωm … 99.9 Ωm

100 Ωm ... 999 Ωm

1.00 kΩm ... 9.99 kΩm

10.0 kΩm ... 99.9 kΩm

100 kΩm ... 9999 kΩm

0.1 Ωm

1 Ωm

0.01 kΩm

0.1 kΩm

1 kΩm

±(5 % of r.) for Re 1 Ω … 1999kΩ

±(10 % of r.) for Re 2 kΩ … 19.99kΩ

±(20 % of r.) for Re > 20 kΩ

                        POWER Power (P, S, Q) 0.00 W (VA, Var) ... 99.9 kW (kVA, kVar)
Power factor -1.00 ... 1.00
Voltage THD 0.1 % ... 99.9 %
                    HARMONICS Voltage harmonics 0.1 V ... 500 V
Voltage THD 0.1 % ... 99.9 %
Current harmonics and Current THD 0.00 A ... 199.9 A
    FIRST FAULT LEAKAGE CURRENT (ISFL) ISC 1, ISC 2 0.0 mA ... 19.9 mA 0.1 mA ±(5 % of r. + 3 digits)
                          IMD TEST Threshold indicative insulation resistance 5 … 640 kΩ 5 kΩ Indicative values, up to 128 steps
                       ILLUMINANCE Type B

0.01 lux ... 19.99 lux

20.0 lux ... 199.9 lux

200 lux ... 1999 lux

2.00 klux ... 19.99 klux

0.01 lux

0.1 lux

1 lux

10 lux

±(5 % of r. + 2 digits)

±(5 % of r.)

Type C

0.01 lux ... 19.99 lux

20.0 lux ... 199.9 lux

200 lux ... 1999 lux

2.00 klux ... 19.99 klux

0.01 lux

0.1 lux

1 lux

10 lux

±(10 % of r. + 3 digits)

±(10 % of r.)

                DISCHARGING TIME Discharging time 0.0 s … 10.0 s 0.1 s ±(5 % of r. + 2 digits)
Peak voltage 0 V … 550 V 1 V ±(5 % of r. + 3 digits)
                         GENERAL Power supply 7.2 V (4400 mAh Li-Ion battery pack)
Overvoltage category 600 V CAT III; 300 V CAT IV
Protection class double insulation
COM port BT, USB, RS232
Weight 1.78 kg
Size ( l x h x w ) 252 x 111 x 165 mm
                            NOTES

1 Measuring current 1 mA ... 3 mA

2 Threshold current 1 mA

3 Itest = 20 A @ 230 V; 16 ... 400 Hz

4 Itest MAX = 0.5 x I∆N

5 UOC < 30 VAC, ISC < 30 mA, f = 15 Hz

Special Installations / Locations

  • Construction Sites
  • Railway Systems
  • Ships / Boats / Marina Places
  • Fire Brigade Vehicles
  • Military / Police Vehicles
  • Mobile LV Generator Units
  • Medical Sites / Surgery Rooms
  • Mobile Video / Audio / Concert Halls / Fair Playground

UK Mainland Order by 2pm for Next Day Delivery*
Under £25.00 £4.50
Over £25.00 FREE

UK Highlands & Islands Order by 2pm for Next Day Delivery*
Under £80.00 £15.00
Over £80.00 FREE

Recently Viewed