Metrel MI3152-ES Multifunction Tester - Entry Set

Product Code: METMI3152ES

Price
£1255.00 ex. VAT £1506.00 inc. VAT

Available In 3-7 Days


Add To Favourites
Detailed Description

Key Features:

  • Predefined Automatic tests:
  • Auto TT (U, Zln, Zs, Uc);
  • Auto TN/RCD (U, Zln, Zs, Rpe);
  • Auto TN (U, Zln, Zlpe, Rpe);
  • Auto IT (U, Zln, Isc, Isfl, IMD).
  • Built-in help screens for referencing on site.
  • Built-in fuse tables for automatic evaluation of the line / loop impedance result.
  • Monitoring of all 3 voltages in real-time.
  • Automatic polarity reversal on continuity test.
  • Automated RCD testing procedure.
  • Built-in charger and rechargeable batteries as standard accessory.
  • BT communication with PC, Android tablets and smart phones via built-in BT.
  • PC SW Metrel ES Manager for creation of test structures and uploading, downloading of test results and report creation.
  • Support for aMESM Android APP, data management tool (option).


*Important Calibration Information:
This instrument comes complete with the manufacturer’s calibration certificate. Please be aware that these certificates are generic and may also be time lapsed. If you would prefer a personalised full traceable calibration certificate applied to the equipment before dispatch, then please select this option from the drop-down menu above, an additional calibration charge will apply.

FREE Gifts

This instrument comes complete with your choice of free gift from the drop-down menu above. Choose from a calibration voucher for next 
year, a 50m R2 wander lead or a set of quality silicone test leads. How about a quality socket tester or lock off kit? 
Whatever you choose you can be sure you're getting a fantastic deal at Instrument Sales & Services.


MI 3152 is an instrument from the new generation of Metrel’s multifunctional measuring instruments.
The already well known functions like complete installation safety testing according to IEC/EN 61557 and AUTO SEQUENCE testing of TN, TT and IT earthing systems are managed by a completely new user interface based on large colour touch screen display. A wide range of functions is included: from on-line voltage monitoring, phase sequence testing, varistor testing, earth resistance measurement, illuminance measurement and TRMS current measurement up to RCD tests, line and loop impedance tests, specific earth resistance measurements as well as ISFL measurements and the IMD tests.

The MI 3152-ES Entry Set Comes Supplied With:

  • nstrument MI 3152 EurotestXC
  • Test lead, 3 x 1.5 m
  • Power supply adapter
  • 6 NiMH rechargeable batteries, type AA
  • Test probe, 3 pcs (blue, brown, green)
  • Crocodile clip, 3 pcs (blue, brown, green)
  • RS232 - PS/2 cable
  • USB cable
  • Soft carrying bag
  • Soft carrying neck belt
  • PC Software Metrel ES Manager (Lite)
  • Short instruction manual
  • Instruction manual on CD
  • Handbook on CD
  • Calibration certificate


Metrel EV Charge

Measuring functions:

  • Insulation resistance with DC voltage from 50 V to 1000 V;
  • Varistor test;
  • Continuity of PE conductors with 200 mA DC test current with polarity change;
  • Continuity of PE conductors with 7 mA test current without RCD tripping;
  • Line/Loop impedance combined also in one function Z AUTO;
  • Loop impedance with Trip Lock RCD function;
  • TRMS voltage and frequency measurements;
  • Phase sequence;
  • Power and THD measurement (up to the 12th harmonic);
  • RCD testing (general and selective, type AC, A, F, B, B+, MI RCD, EV RCD, PRCD, PRCD-K, PRCD-S);
  • Earth resistance (3-wire and 2-clamps method);
  • Specific earth resistance with Ro-adapter (option);
  • TRMS leakage and load currents (option);
  • First fault leakage current (ISFL);
  • Testing of Insulation Monitoring Devices (IMDs);
  • Illumination (option);
  • High resolution Loop impendance (mΩ) (option);
  • EVSE AUTO SEQUENCEs and function inspections;
  • Determining location of cables (option);
  • QR and/or barcode scanner support (option).

Applications:

Electrical Power Systems

  • Power Plants
  • Distribution
  • Safety
  • Connections / Bondings
  • Insulation Analysing
  • Earthings / Funnels

Special Installations / Locations

  • Construction Sites
  • Railway Systems
  • Ships / Boats / Marina Places
  • Fire Brigade Vehicles
  • Military / Police Vehicles
  • Mobile LV Generator Units
  • Medical Sites / Surgery Rooms
  • Mobile Video / Audio / Concert Halls / Fair Playground
Function Measuring Range Resolution Accuracy
Continuity Test Current 7mA 2-wire 0.00 to 19.99Ω 0.1Ω ±5% of r + 3 digits)
20 to 1999Ω
Test Current 200mA 2-wire 0.00 to 19.99Ω 0.01Ω ±3% of r + 3 digits)
20.0 to 199.9Ω 0.1Ω ±5% of r
200.0 to 1999Ω ±5% of r
Insulation Resistance Test Voltage: 50/100/250V 0.00 to 19.99MΩ 0.01MΩ ±5% of r + 3 digits)
20.0 to 99.9MΩ   ±10% of r
100.0 to 199.9MΩ 0.1MΩ ±20% of r
Test Voltage: 500/1000V 0.00 to 19.99MΩ 0.01MΩ ±5% of r + 3 digits
20.0 to 199.9MΩ 0.1MΩ ±5% of r
200 to 999MΩ 1MΩ ±10% of r
RCD RCD Uc 0.00 to 19.99V 0.1V (-0%-15%) of r ±10 digits
20.0 to 99.9V (-0% / +15%) of r
RCD (t) 0.00ms to 40.0ms 0.1ms ±1ms
0.0V max time ±3ms
RCD I Ramp 0.2x lΔN to 1.1x lΔN (AC) 0.05x lΔN ±0.1 x lΔN
0.2 x lΔN to 1.5x lΔN (A), LAN ≥30mA
0.2 x lΔN to 2.2x lΔN (A), lΔN <30mA
0.2x lΔN to 2.2x lΔN (B)
Impedance Z-Line L-L, L-N Ipsc 0.00 to 9.99Ω 0.01Ω ±(5% of r + 5 digits)
10.0 to 99.9Ω 0.1Ω
100 to 999Ω ±(10% of r)
1.00kΩ to 9.99kΩ 10Ω
Zloop L-PE, lpfc 0.00 to 9.99Ω 0.01Ω ±(5% of r + 5 digits)
10.0 to 99.9Ω 0.1Ω
100 to 999Ω ±(10% of r)
1.00kΩ to 9.99kΩ 10Ω
Voltage TRMS 0 to 550V 1V ±(2% of r + 2 digits)
Frequency 0.00 to 9.99Hz 0.01Hz ±(0.2% of r + 1 digit)
10.0 to 499.9Hz 0.1Hz
Current TRMS, AC with A 1018 Clamp 0.0 to 99.9mA 0.1 mA ±(5 % of r. + 5 digits)
100 to 999mA 1 mA ±(3 % of r. + 3 digits)
1.00 to 19.99A 0.01 A ±(3 % of r.)
TRMS, AC with A 1019 Clamp 0.00 to 99.9mA 0.1 mA indicative
100mA to 999mA 1 mA ±(5 % of r.)
1.00 to 19.99A 0.01 A ±(3 % of r.)
TRMS, AC/DC with A 1391 0.00 to 1.99A 0.01 A ±(3 % of r. + 3 digits)
2.00 to 19.99A 0.01 A ±(3 % of r.)
20.0A to 39.9A 0.1 A ±(3 % of r.)
TRMS, AC/DC with A 1391 0.00 to 19.99A 0.01 A indicative
20.0 to 39.9A 0.1 A indicative
40.0 to 299.9A 0.1 A ±(3 % of r. + 5 digits)
Earth Resistance 3 Wire 0.00 to 19.99Ω 0.01Ω ±(5 % of r. + 5 digits)
20 to 199.9Ω 0.2Ω
200.0 to 9999Ω
2 Clamp 0.00 to 19.99Ω 0.01Ω ±(10 % of r. + 10 digits)
20.0 to 30.0Ω 0.1Ω ±(20 % of r.)
30.1 to 39.9Ω 0.1Ω ±(30 % of r.)
Specific Earth Resistance 0.0Ωm to 99.9Ωm 0.1Ωm ±(5 % of r.) for Re 1 Ω to 1999kΩ
100 to 999Ωm 1Ωm
1.00kΩm to 9.99kΩm 0.01kΩm ±(10% of r) for Re 2kΩ to 19.99kΩ
10.0kΩm to 99.9kΩm 0.1kΩm
100kΩm to 9999kΩm 1kΩm ±(20% of r) for Re > 20kΩ
First Fault Leakage Current   0.00 to 19.9mA 0.1mA ±(5% of r + 3 digits)
IMD Test Threshold Indicative Insulation Resistance 5 to 640kΩ 5kΩ Indicative values, up to 128 steps
Illuminance Type B 0.01 to 19.99lux 0.01lux ±(5 % of r. + 2 digits)
20.0 to 199.9lux 0.1lux
200 to 1999lux 1lux ±(5 % of r.)
2.00klux to 19.99klux 10lux
Type C 0.01 to 19.99lux 0.01lux ±(10 % of r. + 3 digits)
20.0 to 199.9lux 0.1lux
200 to 1999 lux 1lux ±(10 % of r.)
2.00 to 19.99klux 10lux
General Specs
Power Supply 9V DC (6 x 1.5V battery or accu, size AA)
Overvoltage Category 1000V DC CAT II; 600V CAT III; 300V CAT IV
Protection Class Double insulation
COM Port BT, USB, RS232
Weight 1.3kg
Size (L x H x W) 230 x 103 x 115mm

Industrial Systems

  • LV Installations Safety / Quality
  • Switchboards / Controlgears
  • Maintenance / Troubleshooting
  • 3-phase system testing

Buildings Facility Management

  • Public areas Safety / Quality
  • Fire Safety

UK Mainland Order by 2pm for Next Day Delivery*
Under £25.00 £4.50
Over £25.00 FREE

UK Highlands & Islands Order by 2pm for Next Day Delivery*
Under £80.00 £15.00
Over £80.00 FREE

Recently Viewed