Product Code: FLIEM54
Available In 3-7 Days
One tool provides all the environmental measurements you need
The FLIR EM54 is ideal for inspecting and troubleshooting HVAC/R ducting systems within residential, commercial, and industrial facilities. This meter can help you verify that duct inlets and outlets have the specified volumetric flow – a prerequisite to an efficient functional system. Featuring humidity, wet bulb, and dew point functions, the EM54 can measure deviations from proper relative humidity levels.
Plus, the included Type-K contact temperature probe is useful to check electric motors and thermal equipment components for proper operating temperatures.
ACCURATE AND RELIABLE
Receive high-quality data consistently, and work without interruption. Using the tripod, place the meter away from objects that may influence
relative humidity measurements.
INSPECT AND TROUBLESHOOT EFFICIENTLY
Work on a wide range of systems more efficiently using the contact temperature probe and wet bulb/dew point calculations.
EASY TO USE
Intuitively operate this simple, ergonomic meter with a backlit display, a ‘hold’ function that freezes readings, and well-marked function keys.
FLIR EM54 Environmental Meter | |||
Measurement | Range | Resolution | Accuracy |
Air Temperature | 30 ~ 60°C (-22 ~ 140°F) | 0.1°C (1°F) | ±1°C (±1.8°F) 10° ~ 30°C (50° ~ 86°F) ±2°C (±3.6°F) -30° ~ 9.9°C (-22° ~ 50°F) and 31° ~ 60°C (88° ~ 140°F) |
Relative Humidity | 5 ~ 98% | 0.1% | ±3.5% |
Dew Point | -30°C ~ 60°C (-22°F ~ 140°F) | 0.1°C (1°F) | F) ±3°C (4.8°F) |
Wet Bulb | -30°C ~ 50°C (-22°F ~ 122°F) | 0.1°C (1°F) | ±3°C (4.8°F) |
K-Type Temperature | -99.9°C ~ 1372°C (-148°F ~ 2502°F) NOTE: The supplied Type-K probe cannot be used to measure temperature > rating printed on the connector |
0.1°C (1°F) | ± (1.5% +1°C [1.8°F]) -99.9° ~ 99.9°C (-148° ~ 212°F) ± (1.5% +2°C [3.6°F]) 100° ~ 1372°C (212° ~ 2502°F) |
Air Velocity | 0.4 ~ 30 (m/s) 79 ~ 5906 (ft/min) 1.4 ~ 108.0 (km/h) 0.9 ~ 67.2 (mph) 0.8 ~ 58.3 (knots) | 0.01 (m/s) 1 (ft/min) 0.1 (km/h) 0.1 (mph) 0.1 (knots) | ± (3% + 0.2 m/s) ± (3% + 39 ft/min) ± (3% + 0.7 km/h) ± (3% + 0.4 mph) ± (3% + 0.4 knots) |
Airflow | 0 ~ 999900 CFM 0 ~ 999900 CMM | 0.001 ~ 100 0.001 ~ 100 | Airflow is a calculation; airflow accuracy is dependent on the air velocity accuracy (specification listed above) |
UK Mainland | Order by 2pm for Next Day Delivery* |
---|---|
Under £25.00 | £4.50 |
Over £25.00 | FREE |
UK Highlands & Islands | Order by 2pm for Next Day Delivery* |
---|---|
Under £80.00 | £15.00 |
Over £80.00 | FREE |
Price £7567.20 £6306.00